XM31-915-HP - 10012310
Batteries
 
 

Alarms
 

Battery
 

Batteries
Battery String Voltage 40.87 V
Battery Balancing Check battery
Balancing String Not balancing
Battery System Configuration 2 strings of 3 batteries each
Battery Temperature 21 °C
70 °F
  1 2 3 Balancing
String A 13.18 V 14.68 V 13.14 V Severe
String B 13.73 V 13.72 V 13.55 V Moderate
Battery Charging
Charger Mode Float
Current Charger Mode Time 6,472 min
Charger Current 0.01 A
Charger Current Limit 10.50 A
Charger Enable Yes
Configuration
Technician ID 0
24 Hour Battery Refresh No
Battery Model Other
Accept Voltage 2.35 V/cell
Float Voltage 2.25 V/cell
Refresh Voltage 2.45 V/cell
Battery Capacity 200 Ah
Temperature Compensation 5.00 mV/cell/°C
HP Battery Rest Mode No
Battery String Detect Auto
Number of Battery Strings 2
Heater Mat Installed No
Conductance
Last Conductance Measurement  
  Last Adjusted Conductance Measurement Manufactured Date
String A Battery 1 0 S(℧)  
String A Battery 2 0 S(℧)  
String A Battery 3 0 S(℧)  
String B Battery 1 0 S(℧)  
String B Battery 2 0 S(℧)  
String B Battery 3 0 S(℧)  

 
Copyright © 2017-2024 EnerSys. All Rights Reserved.